Federal opportunity · Combined Synopsis/Solicitation
ClosedN045--Boiler 3 Oxygen Analyzer and Steam Flow Meter
36C24727Q0050 · Veterans Affairs, Department of · SAM.gov
Closed. Responses were due Oct 26, 2026, 11:00 AM ET.
- Responses due
- Oct 26, 2026, 11:00 AM ET
- Posted
- Oct 22, 2026
- NAICS code
- 238220 · Plumbing, Heating, and Air-Conditioning Contractors
- Place of performance
- Dublin, Ga
- Notice type
- Combined Synopsis/Solicitation
- Solicitation number
- 36C24727Q0050
- Official notice
- View on SAM.gov →
Similar open opportunities
- J043--Damen Sump Pump Control System RepairVeterans Affairs, Department of · Due Nov 6, 2026 · Under a day left
- N048-- B41 Isolation Valve InstallationVeterans Affairs, Department of · Due Nov 9, 2026 · 2 days left
- J048--NEW - Energy Center Steam Header& Boilers valves, gaskets, and vent replacementVeterans Affairs, Department of · Due Nov 9, 2026 · 3 days left
- Rental of Two Chillers for One YearVeterans Affairs, Department of · Due Nov 10, 2026 · 3 days left
- J041--White City B249 SE HVAC RepairVeterans Affairs, Department of · Due Nov 10, 2026 · 4 days left
- J045--Glycol Loop Flushing - NWIVeterans Affairs, Department of · Due Nov 10, 2026 · 4 days left
What the agency was buying
Questions and Answers 36C24727Q0050 Boiler #3 Oxygen Analyzer and Steam Flow Meter RFI Responses Where should the output signals from the new steam flow meter and O2 analyzer terminate? For example, the existing building automation system (BAS), the existing Boiler 3 burner/boiler controls, or a local display only. Burner 3 boiler/burner controls where applicable and local display.
Does the government require active O2 trim control to the burner fuel/air ratio, or monitoring and display of the O2 only? Oxygen analyzer must send signals/information to combustion controls to control trim. What is the material of construction for the stack?
Is it single or double wall? Stack is double walled. Inside material is steel; outside material is galvanized steel.
Stack is 36 D Selkirk Metalbestos Model P.S. Current operating pressure and temperature of the system for boiler #3? Design pressure is 200 psi. Typical operating pressure is 82 psi. Typical operating temperature is about 330 degrees Fahrenheit.
What are the available outputs on the physical steam flow meter (e.g., 4-20 mA, Modbus RTU, BACnet MS/TP)? 4-20 mA analog. Is the flow meter wired directly into an analog terminal block on the CB Hawk, or is it wired directly to the facility s Building Automation System (BMS)? Steam flow meter is wired into local CB Hawk analog terminal block. Please provide nameplates for the existing oxygen analyzer and steam flow meter.
Oxygen analyzer nameplate: Steam flow meter nameplate: